Eastron SDM630 TCP
The Eastron SDM630 TCP is a three-phase kWh meter that the CEMM reads over the network. There is a direct-connected version, where the current flows through the meter itself, and a version that measures via current transformers, recognisable by CT in the type name. You use the latter for larger currents.
Installing the meter
- Have an electrician install the meter in the fuse box, for the circuit you want to monitor.
- Are you measuring consumption or a battery? Then connect the grid side to the input of the meter and the output to the appliance side. Are you measuring production? Then it is the other way round: the input is on the inverter side and the output on the grid side.
- Are you using a CT version? Then place the current transformers with the same current direction: P1 on the grid side and P2 on the appliance side, or the other way round for production. The arrow on the current transformer then points towards the appliances. Make sure each current transformer is on the correct phase.
- Connect the meter to the same network as the CEMM. Set an IP address and make a note of it for the next step.
Setting up current transformers (CT versions only)
A CT version needs to know which current transformers you are using, otherwise the measured energy will be wrong. Set the ratio of the current transformers (for example 100/5) in the settings menu of the meter. You can find the ratio on the current transformer itself.
Adding the meter
- Activate the Modbus module with your activation code, if you have not done so already.
- In the portal or the app, go to Settings › Meters and click Add meter.
- Choose Modbus TCP meter and then the Eastron SDM630 meter. This also applies to the CT version.
- Enter the IP address of the meter.
- Complete the remaining steps of the wizard.
Do you also want to log the voltage, current or power per phase? How to log extra data.
Problem?Consumption and export are reversed
The meter or a current transformer has been installed the wrong way round. If it is not (or no longer) possible to change the physical installation, you can reverse the direction in the CEMM: go to Settings › Meters, click Settings next to the meter and change the Measurement direction.
Problem?The meter measures both consumption and export
Does a CT version measure consumption and export at the same time, while the current can only flow in one direction? Then one or two current transformers have been installed the wrong way round. Each current transformer has an arrow that shows the current direction. For consumption, the arrow points towards the appliances; for production, towards the grid. Have the current transformers that are the wrong way round physically turned around, so that all arrows point in the same direction. The Measurement direction in the CEMM does not solve this, because it reverses all phases at once.
Still stuck? Contact support